One-Way Flow Altitude Valve with Solenoid Override
Series LFF127-32, LFF1127-32 One Way Flow Altitude Valve with Solenoid Override Feature is designed to open, allowing flow into a reservoir or elevated storage tank (tank fill), and close drip tight when high water level is achieved, or as commanded by the Solenoid Pilot. It controls water level by remotely sensing static tank head pressure through a field installed sensing line, and opens when the level is below the adjustable setpoint and closes drip tight when the level is above the adjustable setpoint, or as commanded by the Solenoid Pilot. The Solenoid also has provisions for manual operation in the event of power outage.
Features
- Allows flow into a reservoir or elevated storage tank
- Water level is controlled by a field installed sensing line
- Solenoid Pilot offers override capability
- Body and cover are constructed of strong and durable ductile iron (ASTM A536)